Difference between revisions of "Category:715 Vertical Drain at End Bents"

From Engineering_Policy_Guide
Jump to navigation Jump to search
m (updated links)
 
m (Per CM, removed archaic SiteManager info and replaced with AASHTOWARE info)
 
Line 10: Line 10:
  
 
===715.2.3 Report (Records)===
 
===715.2.3 Report (Records)===
Reports of vertical drain and drainpipe are to be made through SiteManager and the certifications are to be retained in the district office.
+
Reports of vertical drain and drainpipe are to be made through AASHTOWARE Project (AWP) and the certifications are to be retained in the district office.
  
 
==715.3 Laboratory Testing for Sec 715==
 
==715.3 Laboratory Testing for Sec 715==
 
No additional guidance - refer to [http://www.modot.org/business/standards_and_specs/SpecbookEPG.pdf#page=11 Standard Specification 715].
 
No additional guidance - refer to [http://www.modot.org/business/standards_and_specs/SpecbookEPG.pdf#page=11 Standard Specification 715].

Latest revision as of 10:22, 1 October 2021

715.1 Construction Inspection for Sec 715

No additional guidance - refer to Standard Specification 715.

715.2 Materials Inspection for Sec 715

715.2.1 Vertical Drain

Vertical drain will be accepted on the basis of a manufacturer's certification in accordance with Standard Specification 1012.

715.2.2 Drain Pipe

Corrugated metal drainpipe will be accepted in accordance with Standard Specification 1020. Corrugated Polyvinyl Chloride (PVC) drainpipe and Corrugated Polyethylene (PE) drainpipe will be accepted on the basis of the manufacturer's certification and visual inspection in accordance with Standard Specification 1013.

715.2.3 Report (Records)

Reports of vertical drain and drainpipe are to be made through AASHTOWARE Project (AWP) and the certifications are to be retained in the district office.

715.3 Laboratory Testing for Sec 715

No additional guidance - refer to Standard Specification 715.

This category currently contains no pages or media.