751.32 Concrete Pile Cap Intermediate Bents

From Engineering_Policy_Guide
Revision as of 09:12, 15 April 2010 by Smithk (talk | contribs) (attached article to new EPG 751)
Jump to navigation Jump to search

751.32.1 General

751.32.1.1 Material Properties

Concrete
Typically, shall consist of:
  Class B Concrete (Substructure) = 3.0 ksi
    = 10

In addition, Class B-1 Concrete (Substructure) may also be used in special cases (See Project Manager). The following equations shall apply to both concrete classes:

Concrete modulus of elasticity:

Where:

= unit weight of non-reinforced concrete = 0.145 kcf
= correction factor for source of aggregate = 1.0


Modulus of Rupture: For minimum reinforcement,
  For all other calculations,
 is in units of ksi    


Reinforcing Steel

Minimum yield strength, = 60.0 ksi
Steel modulus of elasticity, = 29000 ksi

751.32.2 Design

751.32.2.1 Limit States and Factors

In general, each component shall satisfy the following equation:

Where:

= Total factored force effect
= Force effect
= Load modifier
= Load factor
= Resistance factor
= Nominal resistance
= Factored resistance


Limit States

The following limit states shall be considered for bent design:

STRENGTH – I
STRENGTH – III
STRENGTH – IV
STRENGTH – V
SERVICE – I
FATIGUE

See LRFD Table 3.4.1-1 and LRFD 3.4.2 for Loads and Load Factors applied at each given limit state.


Resistance factors

STRENGTH limit states, see LRFD 5.5.4.2
For all other limit states, = 1.00


Load Modifiers

751.32.3 Details

751.32.3.1 General

(*) 3" (Typ.)
Part Elevation Part Section
Use 2'-6" minimum or as determined by the superstructure requirements or the minimum support length required for earthquake criteria (expansion joint bents only) (3" increments).
= 2'-9" (Min.) for Wide Flange and Double-Tee Girders or,
   3'-0" (Min.) for Prestressed Girders and Plate Girders.
Check the clearance of the anchor bolt well to the top of pile. Increase the beam depth if needed.
If the depth at the end of the beam, due to the steps, exceeds 4~6", the beam bottom should be stepped or sloped.
Use 3/4" drip groove where expansion device is located at bent. Continue to use 1-1/2" clear to reinforcing steel in bottom of beam. 3/4" drip groove shall be formed continuously around all piling at 3" from edge of beam.
Minimum of 3 piles at 10'-0" cts., maximum spacing (1" increments).

751.32.3.2 Front Sheet

Note: The following are details and dimensions for the Plan View on the Front Sheets.
  Details for unsymmetrical roadways will require dimensions tying Centerline Lane to Centerline Structure.


751.32.4 Reinforcement

751.32.4.1 General

Part Elevation Section Thru Beam
 
 
Part Plan  
Note: Locate #4 bars "" under bearings where required to maintain a 6" maximum spacing of combined stirrups. (#4 bars "" are not required for Double-Tee Structures.)
  When an expansion device is used at an intermediate bent, all reinforcement located entirely within the beam or extending into the beam shall be epoxy coated.


* #4 Bars () not required for Double-Tee structures
Reinforcement Under Bearings
 
Transverse Beam Steps - Over 3"
or Steps Accumulating Over 3"


Part Plan
 
Over 3" thru 12" Over 12"
Longitudinal Beam Steps